4.4.2

Aux Contacts - Output

The Output terminal strip TN2 provides eight (OUT1 thru OUT8) Form "A" NO (Normally Open) dry type
programmable contacts to drive annunciation signals sourced or "wetted" by external monitoring devices. All
output contacts are rated for NEC Class 2 operation (30VDC / 1ADC.)
The output dry contacts should be operated at their rated values or lower. Figure 4-20 illustrates a typical
installation. The external relay can be a lamp, LED, computer, etc.
These contacts can be programmed to provide any of the functions in Table 4-2.
UPS Cabinet
Relay
Contact
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Stops the rectifier converter remotely.
For use with the internal wave capture tool; for use by Authorized Toshiba
Service Providers.
Terminal
Terminal

Figure 4-20 Control Wiring for Aux Output Contacts

Description
External to UPS
Cabinet
Relay
Coil
NEC Class 2
Power Source
User supplied