Toshiba G9000 SERIES Installation And Operation Manual page 49

480/480 v 100/160/225/300/500/750 kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

Code
Function
13
FAULT GROUP 2
14
BYPS.SYNCHRONOUS
15
BYPS.ASYNCHRONOUS
16
REMOTE OPE.ENABLE
17 *
LOAD ON INVERTER
18 *
LOAD ON BYASS
19
LOAD ON AC
20 *
BATTERY OPERATION
21 *
CONVERTER OPERATION
22
INVERTER OPERATION
23
CB1 CLOSE
24
CB2 CLOSE
25
52S CLOSE
26
POWER DEMAND ON
27
EQUALIZING CHARGE
28
ANOTHER BUS SYNC.OK
*Default output settings
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Activated when the preset group of alarms (Fault Group 2) all occur to the
system at once. These groups are set in the TEST MENU by an Authorized
Toshiba Service Provider.
Activated when the inverter voltage and bypass voltage are synchronous.
Activated when the inverter voltage and bypass voltage are asynchronous.
Activated when any remote operation occurs (Stop/Start Inverter, etc.)
Activated when the power is supplied from the inverter. This is the default
setting on OUT2.
Activated when the power is supplied from the inverter. This is the default
setting on OUT1.
Activated when the power is supplied from the input via the UPS's
rectifier/converter - inverter.
Activated when the battery is operating following an AC power failure. This is
the default setting on OUT3.
Activated when the converter is operating. This is the default setting on
OUT4
Activated when the inverter is operating.
Activated when CB1 (Input Contactor) is closed.
Activated when CB2 (Battery Breaker) is closed.
Activated when 52S (Bypass Contactor) is closed.
Activated when a Power Demand is activated by one of the Inputs.
Activated when the UPS is charging the batteries at the equalizing charge
level. This command boosts the charge voltage (500-640 V) for a preset
duration (0-100 hr.)
Annunciates that the UPS is successfully synchronized to an external source
Description