Installation
3

Illustration 2.19 Location of DIP Switches

1
S201 - terminal 53
2
S202 - terminal 54
3
S801 - standard bus termination
4
Profibus termination
5
Fieldbus address
NOTE
Switches 4 and 5 are only valid for units fitted with
fieldbus options.

2.4.14 Serial Communication

Connect RS-485 serial communication wiring to terminals
(+)68 and (-)69.
Switch S801 (BUS TER.) can be used to enable
termination on the RS-485 port (terminals 68 and
69). See Illustration 2.19.
Shielded serial communication cable is
recommended
See 2.4.11 Earth (Grounding) Requirements for
proper grounding
Two communication protocols are internal to the
frequency converter
Danfoss FC
Modbus RTU
For basic serial communication setup, select the
following
Protocol type in 8-30 Protocol
Frequency converter address in
8-31 Address
Baud rate in 8-32 FC Port Baud Rate
Functions can be programmed remotely using
the protocol software and RS-485 connection or
in parameter group 8-** Communications and
Options
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
®
VLT
Decentral Drive FCD 302 Operating Instructions
1
2
4
5
®
MG04F302 - VLT
is a registered Danfoss trademark
Selecting a specific communication protocol
changes various default parameter settings to
match that specifications of the protocol along
with making additional protocol-specific
parameters available
Control card options are available to provide
additional communication protocols. See the
option-card documentation for installation and
operation instructions
Profibus
Ethernet IP
ProfiNet

2.4.15 Connection to PC

To control the frequency converter from a PC, install the
MCT 10 Set-up Software.
The PC is connected via a standard (host/device) USB
cable, or via the RS-485 interface.

Illustration 2.20 Electronic Part

CAUTION
The USB connection is galvanically isolated from the
supply voltage (PELV) and other high-voltage terminals.
The USB connection is not galvanically isolated from
protection earth. Use only isolated laptop/PC as connection
to the USB connector on frequency converter or an
isolated USB cable/converter.

2.4.16 Safe Stop

The FCD 302 provides safe stop functionality via control
terminal 37. Safe stop disables the control voltage of the
power semiconductors of the frequency controller output
stage. This in turn prevents generating the voltage
required to rotate the motor. When the Safe Stop (T37) is
2