Number
Cause
F08700
Communications error
F13100
Know-how protection: Copy
protection error
F13101
Know-how protection: Copy
protection cannot be activated
F30001
Overcurrent
F30002
DC-link voltage overvoltage
F30003
DC-link voltage undervoltage
F30004
Converter overtemperature
F30005
I2t converter overload
SINAMICS G120C converter
Getting Started, 04/2014, FW V4.7, A5E34264105B AA
Remedy
A CAN communications error has occurred. Check the following:
Bus cable
•
Baud rate (p8622)
•
Bit timing (p8623)
•
Master
•
Start the CAN controller manually with p8608 = 1 after the cause of the fault
has been resolved!
The know-how protection and the copy protection for the memory card are
active. An error occurred during checking of the memory card.
Insert a suitable memory card and switch the converter supply voltage
•
temporarily off and then on again (POWER ON).
Deactivate the copy protection (p7765).
•
Insert a valid memory card.
Check the following:
Motor data, if required, carry out commissioning
•
Motor's connection method (Υ / Δ)
•
U/f operation: Assignment of rated currents of motor and Power Module
•
Line quality
•
Make sure that the line commutating reactor is connected properly
•
Power cable connections
•
Power cables for short-circuit or ground fault
•
Power cable length
•
Line phases
•
If this doesn't help:
U/f operation: Increase the acceleration ramp
•
Reduce the load
•
Replace the power unit
•
Increase the ramp-down time (p1121).
Set the rounding times (p1130, p1136).
Activate the DC link voltage controller (p1240, p1280).
Check the line voltage (p0210).
Check the line phases.
Check the line voltage (p0210).
Check whether the converter fan is running.
Check whether the ambient temperature is in the permissible range.
Check whether the motor is overloaded.
Reduce the pulse frequency.
Check the rated currents of the motor and Power Module.
Reduce current limit p0640.
When operating with U/f characteristic: Reduce p1341.
Fault rectification
5.1 List of alarms and faults
63