Number
Cause
F07320
Automatic restart aborted
A07321
Automatic restart active
F07330
Search current measured too
low
A07400
V
controller active
DC_max
A07409
V/f control current limiting
controller active
F07426
Technology controller actual
value limited
F07801
Motor overcurrent
A07805
Drive: Power unit overload I2t
F07807
Short circuit detected
A07850
External alarm 1
F07860
External fault 1
F07900
Motor blocked
SINAMICS G120C converter
Getting Started, 04/2014, FW V4.7, A5E34264105B AA
Remedy
Increase the number of restart attempts (p1211). The current number of
start attempts is shown in r1214.
Increase the wait time in p1212 and/or monitoring time in p1213.
Create ON command (p0840).
Increase the monitoring time of the power unit or switch off (p0857).
Reduce the wait time for resetting the fault counter p1213[1] so that fewer
faults are registered in the time interval.
Explanation: The automatic restart (AR) is active. During voltage recovery
and/or when remedying the causes of pending faults, the drive is
automatically switched back on.
Increase search current (P1202), check motor connection.
If the controller is not to intervene:
Increase the ramp-down times.
Deactivate the V
DC_max
for V/f control).
The alarm automatically disappears after one of the following measures:
Increase the current limit (p0640).
Reduce load.
Increase the ramp-up time to the speed setpoint.
Adapt the limits to the signal level (p2267, p2268).
Check the actual value scaling (p2264).
Check current limits (p0640).
U/f control: Check the current limiting controller (p1340 ... p1346).
Increase acceleration ramp (p1120) or reduce load.
Check motor and motor cables for short circuit and ground fault.
Check motor for star-delta connection and rating plate parameterization.
Check power unit / motor combination.
Select flying restart function (p1200) if switched to rotating motor.
Reduce the continuous load.
Adapt the load cycle.
Check the assignment of rated currents of the motor and power unit.
Check the converter connection on the motor side for any phase-phase
short-circuit.
Rule out that line and motor cables have been interchanged.
The signal for "external alarm 1" has been triggered.
Parameter p2112 defines the signal source of the external alarm.
Remedy: Rectify the cause of this alarm.
Remove the external causes for this fault.
Make sure that the motor can rotate freely.
Check the torque limit: r1538 for a positive direction of rotation; r1539 for
a negative direction of rotation.
5.1 List of alarms and faults
controller (p1240 = 0 for vector control, p1280 = 0
Fault rectification
61