Installing
3.2 Connecting
2. Connect the inverter and its components.
The plugs for connecting the line supply,
motor, and braking resistor can be found on
the lower side of the inverter.
3. If an EMC-compliant installation is required,
you must use shielded cables. See also
section: Installing the converter in compliance
with EMC rules (Page 21).
You have now connected the inverter and its components.
Components for United States / Canadian installations (UL/CSA)
This equipment is capable of providing internal motor overload protection according to
UL508C. Take the following actions In order to comply with UL508C:
● Use UL/CSA-certified J-type fuses, overload circuit-breakers or intrinsically safe motor
protection devices.
● For each frame size A to C use class 1 75° C copper wire only.
● Install the converter with any external recommended suppressor with the following
features:
– Surge-protective devices; device shall be a Listed Surge-protective device (Category
– Rated nominal voltage 480/277 V
– Clamping voltage V
– Suitable for Type 1 or Type 2 SPD application.
– Clamping shall be provided between phases and also between phase and ground.
● Do not change the parameter p0610 (factory setting of p0610 = 12 means: the drive
reacts on a motor overtemperature with an immediate alarm and after a certain time with
a fault).
20
code VZCA and VZCA7).
= 2000 V, I
PR
, 50/60 Hz, 3-phase.
AC
= 3 kA min, MCOV = 508 V
N
Getting Started, 04/2014, FW V4.7, A5E34264105B AA
, SCCR = 40 kA.
AC