Default setting 15: Switch over between analog setpoint and motorized
potentiometer (MOP) using DI 3
Selected with
STARTER: Process industry
•
BOP-2: Proc
•
Fieldbus interface is not active.
Default setting 19: Three-wire control
with method 1
Selected with
STARTER: 3-wire
•
(enable/forward/backward)
BOP-2: 3-wIrE 1
•
Fieldbus interface is not active.
SINAMICS G120C converter
Getting Started, 04/2014, FW V4.7, A5E34264105B AA
Fieldbus interface is not active.
Default setting 20: Three-wire control
with method 2
Selected with
STARTER: 3-wire
•
(enable/on/reverse)
BOP-2: 3-wIrE 2
•
Fieldbus interface is not active.
3.2 Connecting
Default setting 17: Two-wire control
with method 2
Selected with
STARTER: 2-wire
•
(forward/backward 1)
BOP-2: 2-wIrE 1
•
Default setting 18: Two-wire control
with method 3
Selected with
STARTER: 2-wire
•
(forward/backward 2)
BOP-2: 2-wIrE 2
•
Fieldbus interface is not active.
Default setting 21: Fieldbus USS
Selected with
STARTER: USS fieldbus
•
BOP-2: FB USS
•
Default setting 22: Fieldbus CANopen
Selected with
STARTER: CAN fieldbus
•
BOP-2: FB CAN
•
USS setting: 38400 baud, 2 PZD, PKW
variable
CANopen setting: 20 kBaud
Installing