Commissioning
4.2 Commissioning with BOP-2 operator panel
Defining the function of an analog input
Procedure
To define the function of an analog input, proceed as follows:
1. Select the function marked using a CI parameter.
2. Enter the parameter number of analog input 755[00] into the CI parameter.
3. Determine whether the analog input is a current or a voltage input:
– Set the I/U switch at the front of the inverter to the correct position.
– Set the p0756[00] parameter to the corresponding value.
You have now defined the analog input function.
Example: You want to enter the supplementary setpoint via AI 0.
Advanced settings
When switching over the master control of the inverter (for example, if you select default
setting 7), you must select the correct index of the parameter:
● Index 0 (e.g. p1075[00]) applies to the assignment for the interface on the left-hand side
of the macro representation.
● Index 1 (e.g. P1075[01]) applies to the assignment for the interface on the right-hand side
of the macro representation.
Defining the function of a digital output
Procedure
To define the function of a digital output, proceed as follows:
1. Select the function marked using a BO parameter.
2. Enter the number of the BO parameter into parameter p073x of the digital output.
You have defined the digital output function.
Example: You want to report a "fault" signal via the DO 1.
40
SINAMICS G120C converter
Getting Started, 04/2014, FW V4.7, A5E34264105B AA
Setting in BOP-2:
Setting in BOP-2: