Daylight Sensor Setup

Group Mode

This step allows you to assign daylight sensors to a group of DALI loads connected
to the GRAFIK Eye
QS control unit.
®
Set Up Groups
Daylight Sensor
1. If not already done, complete the steps on page 17, and
Daylight Groups
select "Group Mode".
2. Use the Master buttons to highlight "Daylight Groups" and
Setup
press the OK button to accept.
3. Use the Master buttons to scroll through the list of available
Configure Groups
daylight groups. Up to 16 groups of DALI loads can be
defined. Press the OK button to accept.
4. Use the Master buttons to scroll through the DALI devices on
Group 1
the link. Press the OK button to add or remove the selected
device. The currently selected device will display its current
assignment status:
Group 1
Unassigned if it is not assigned to any group
Assigned if it is assigned to the selected (displayed) group
Ballast 2/23
Group x if it is currently assigned to another group (x = the
group number it is assigned to)
*Unassigned*
5. Press the Timeclock (back) button to return to the list of
configurable groups, and repeat these steps to assign devices
OR
to other groups.
Group 1
Note: Each DALI device can be assigned to only one group.
Assigning a device already associated with another group will
Ballast 2/23
replace its existing programming.
*Assigned*
OR
Group 1
Ballast 2/23
*Group 2*
®
1
9
2
10
3
11
4
12
(continued on next page)
For additional information, see the complete installation and operation guide at www.lutron.com/qs
GRAFIK Eye
5
13
6
14
7
15
8
16
9-16
1-8
QS with DALI Quick Installation and Operation Guide 19
®