Ambient Conditions; Materials - ABB PVS800-57B Hardware Manual

Solar central inverters
Hide thumbs Also See for PVS800-57B:
Table of Contents

Advertisement

Ambient conditions

Installation site altitude
Air temperature
Relative humidity
Environmental category
Wet conditions
Pollution degree
Contamination levels
(IEC 60721-3-3,
IEC 60721-3-2,
IEC 60721-3-1)
Atmospheric pressure
Vibration (IEC 60068-2)
Shock (IEC 60068-2-27)
Free fall

Materials

Cabinet
Air filters on the cabinet
door
Busbars
Fire safety of materials
(IEC 60332-1)
Environmental limits for the inverter are given below. The inverter is to be
used in indoor environment.
Note: If the installation has ventilation ducts directly to outdoors, the back
flow of moist and dusty air must be prevented.
Operation
installed for stationary
use
0 to 3000 m (9842 ft)
Above 1000 m (3281 ft),
see section
Altitude
derating
on page
48.
-20 °C to +50 °C (-4 °F
to +104 °F). No
condensation allowed.
Output derated in the
range +50 °C to +60 °C
(+104 °F to +122 °F).
See section
Derating
(page 47). If the
operating temperature
falls below 0 °C (32 °F),
cabinet heater option
G300 has to be used. No
frost allowed.
5 to 95%
Indoor conditioned
Not to be used in wet locations. The installation location must be dry.
2. Normally only non-conductive pollution is allowed.
No conductive dust allowed.
Chemical gases:
Class 3C1
Solid particles:
Class 3S2
61.6 to 106 kPa
0.7 to 1.05 atmospheres
Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
2
2
max. 7 m/s
(23 ft/s
)
(13.2 to 100 Hz)
sinusoidal
Not allowed
Not allowed
Hot-dip zinc-coated (thickness approximately 20 micrometers) steel sheet
(thickness 1.5 mm) with polyester thermosetting powder coating (thickness
approximately 80 micrometers) on visible surfaces except back panel.
Color: RAL 7035 (light beige, semigloss).
AIR-TEX G-150
Tin-plated copper or aluminum
Insulating materials and non-metallic items: mostly self-extinguishing
Storage
in the protective
package
-
-40 to +70 °C
(-40 to +158 °F)
Max. 95%
Chemical gases:
Class 1C2
Solid particles:
Class 1S3
70 to 106 kPa
0.7 to 1.05 atmospheres
Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
2
2
max. 7 m/s
(23 ft/s
)
(13.2 to 100 Hz)
sinusoidal
2
Max. 100 m/s
2
(330 ft/s
), 11 ms
Not allowed
Technical data 57
Transportation
in the protective
package
-
-40 to +70 °C
(-40 to +158 °F)
Max. 95%
Chemical gases:
Class 2C2
Solid particles:
Class 2S2
60 to 106 kPa
0.6 to 1.05 atmospheres
Max. 3.5 mm (0.14 in.)
(2 to 9 Hz),
2
2
max. 15 m/s
(49 ft/s
)
(9 to 200 Hz) sinusoidal
2
Max. 100 m/s
2
(330 ft/s
), 11 ms
Not allowed

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents