Siemens CPU 412-1 Instruction Manual page 131

S7-400; cpu 412 series; cpu 414 series; cpu 416 series; cpu 417 series;
Hide thumbs Also See for CPU 412-1:
Table of Contents

Advertisement

SFC
SFC Name
No.
58
WR_REC
Write parameter data record
local (n = number of bytes)
First call, integrated DP interface module
(n = number of bytes)
Intermediate call, REQ = 0
integrated DP interface module
Last call, integrated DP interface module
First call, external DP interface module
(n = number of bytes)
Intermediate call, REQ = 0
external DP interface module
Last call, external DP interface module
S7-400 Instruction List
A5E00267845-01
Function
279 +
n * 3
283 +
n * 0.1
112
114
277 +
n * 0.06
113
115
Execution Time in ms
CPU
CPU
CPU
412
414
416
170 +
120 +
n * 2.5
n * 2.3
168 +
113 +
n * 0.04
n * 0.03
66
45
67
45
163 +
109 +
n * 0.06
n * 0.04
67
45
68
46
System Functions
CPU
CPUs
CPUs
417
414-4H
414-4H
417-4H
417-4H
(solo)
(redun-
dant)
107 +
xx +
xx +
n * 2.2
n * yy
n * yy
97 +
xx +
xx +
n * 0.03
n * yy
n * yy
38
xx
xx
38
xx
xx
96 +
xx +
xx +
n * 0.03
n * yy
n * yy
40
xx
xx
40
xx
xx
129

Hide quick links:

Advertisement

Table of Contents
loading