Parameterization
Parameter
Submenu
Current output 2
Output of
Qm
Qv → l = 100 %
120.00 l/min
Density → l = 0 %
0.8 kg/l
Density → l = 100 %
1.3 kg/l
Temp → l = 0 %
-50.00 °C
78
Value range / input type
Qm
Table
Qv
Density
Temperature
Concentration
Qm Concentration
0.1 ... 10000000
float
3
float
0.5 ... 3.5 g/cm
3
float
0.5 ... 3.5 g/cm
-50 ... 180
float
CoriolisMaster FCM2000
Note
In contrast to current output 1, current output 2 is
not HART-enabled and has a fixed current output
range (4 ... 20 mA). In submenu current output 2,
dependent on the measurement variable to be
assigned to the output, only those menus are
displayed which are required for configuring the
output. Current output 2 is always passive.
Not contained in the fieldbus software versions.
The selections in this menu are used to define
which of the following variables is to be used for
current output 2.
In this menu the volume flowrate value is entered
for which the current output is to indicate its
100 % value (20 mA). The menu is only displayed
when the current output is based on the volume
flowrate.
Maximum value: QmMax / minimum density
3
(0.5 g/cm
)
In this menu the density value is entered for which
the current output is to indicate its 0 % value
(4 mA). The menu is only displayed when the
current output is based on the density.
3
Minimum:
0.5 g/cm
3
Maximum:
3.5 g/cm
The density value for a current output value of
100 % must be at least 0.01 g/cm
density value for a current output value of 0 %
In this menu the density value is entered for which
the current output is to indicate its 100 % value
(20 mA). The menu is only displayed when the
current output is based on the density.
3
Minimum:
0.5 g/cm
3
Maximum:
3.5 g/cm
The density value for a current output value of
100 % must be at least 0.01 g/cm
density value for a current output value of 0 %
In this menu the temperature value is entered for
which the current output is to indicate its 0 %
value (4 mA). The menu is only displayed when
the current output is based on the temperature.
Minimum:
-50 °C
Maximum:
180 °C
The temperature value for a current output value
of 100 % must be at least 10 °C larger than the
temperature value for a current output value of
0 %.
3
larger than the
3
larger than the
D184B111U02