ABB CoriolisMaster FCM2000 Operating Instructions Manual page 43

Mass flowmeter
Hide thumbs Also See for CoriolisMaster FCM2000:
Table of Contents

Advertisement

Pos: 31.3.11 /Technische Daten / Datenblatt/Durchfluss/FCM2000/Elektrischer Anschluss/PROFIBUS PA/FOUNDATION Fieldbus @ 5\mod_1167922688843_3101.doc @ 56380 @ 5
PROFIBUS PA / FOUNDATION Fieldbus, supply power
1+
2-
L
N
1
Fig. 43
1
Supply power
Line voltage: U
100 ... 230 V AC, frequency 50/60 Hz,
AC
terminals L, N,
Low voltage: U
24; frequency 50/60 Hz, terminals 1+, 2-
AC
Low voltage:
U
24 V
DC
2a PROFIBUS PA design according to IEC 61158-2 (Profile 3.0)
U = 9 ... 32 V
I = 14 mA (normal operation)
I = 26 mA (in the event of error/FDE)
Terminals: 97 / 98
Connection example via M12 plug, see Fig. 39
Pos: 31.4 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830 @
D184B111U02
97 98
2
2-
1+
97 98
N
L
2
1
CoriolisMaster FCM2000
3
3
3
3
3
3
2b FOUNDATION Fieldbus design according to IEC 61158-2
U = 9 ... 32 V
I = 14 mA (normal operation)
I = 26 mA (in the event of error/FDE)
Terminals: 97 / 98
Connection example via M12 plug, see Fig. 39
3
Functional ground
Installation
MC23
ME21
ME22
ME23
3
MC21
MS21
G00348