Parameterization
Parameter
Qv → l = 100 %
120.00 l/min
Density → l = 0 %
500.00 g/l
Density → l = 100 %
1000.00 g/l
Temp → l = 0 %
-10.0 °C
Temp → l = 100 %
180 °C
Qm% → l = 100 %
120 kg/min
76
Value range / input type
0.1 ... 10000000
float
3
float
0.5 ... 3.5 g/cm
3
float
0.5 ... 3.5 g/cm
-50 ... 180 °C
float
-50 ... 180 °C
float
CoriolisMaster FCM2000
Note
In this menu the volume flowrate value is entered
for which the current output is to indicate its
100 % value (20 mA). The menu is only displayed
when the current output is based on the volume
flowrate.
Maximum value: QmMax / minimum density
3
(0.5 g/cm
)
In this menu the density value is entered for which
the current output is to indicate its 0 % value
(0 mA or 4 mA). The menu is only displayed when
the current output is based on the density.
3
Minimum:
0,5 g/cm
3
Maximum:
3,5 g/cm
The density value for a current output value of
100 % must be at least 0.01 g/cm
density value for a current output value of 0 %.
In this menu the density value is entered for which
the current output is to indicate its 100 % value
(20 mA). The menu is only displayed when the
current output is based on the density.
3
Minimum:
0,5 g/cm
3
Maximum:
3,5 g/cm
The density value for a current output value of
100 % must be at least 0.01 g/cm
density value for a current output value of 0 %
In this menu the temperature value is entered for
which the current output is to indicate its 0 %
value (0 mA or 4 mA). The menu is only displayed
when the current output is based on the
temperature.
Minimum:
-50 °C
Maximum:
180 °C
The temperature value for a current output value
of 100 % must be at least 10 °C larger than the
temperature value for a current output value of
0 %.
In this menu the temperature value is entered for
which the current output is to indicate its 100 %
value (20 mA). The menu is only displayed when
the current output is based on the temperature.
Minimum:
-50 °C
Maximum:
180 °C
The temperature value for a current output value
of 100 % must be at least 10 °C larger than the
temperature value for a current output value of
0 %.
Only displayed for "Output of Qn Conc." Net
massflow at current output 100 %.
3
larger than the
3
larger than the
D184B111U02