ABB CoriolisMaster FCM2000 Operating Instructions Manual page 42

Mass flowmeter
Hide thumbs Also See for CoriolisMaster FCM2000:
Table of Contents

Advertisement

Installation
Pos: 31.3.9 /Technische Daten / Datenblatt/Durchfluss/FCM2000/Elektrischer Anschluss/Ein- / Ausgangssignale ME2 / MS2 @ 8\mod_1176817364515_3101.doc @ 83873 @ 5
Input and output signals, supply power ME2/MS2
51 52 81 82 41 42 31 32 33 34
4
5
Fig. 42
1
Supply power
Line voltage: U
100 ... 230 V AC, frequency 50/60 Hz,
AC
terminals L, N,
Low voltage: U
24; frequency 50/60 Hz, terminals 1+, 2-
AC
Low voltage:
U
24 V
DC
2
Current output 1: selectable in software
2a: Function: Active
Terminals: 31, 32; 0/4 ... 20 mA (0 Ω ≤ R
2b: alternate function: passive (option D)
Terminals: 31, 32; 4 ... 20 mA (0 Ω ≤ R
Source voltage 12 ≤ U
≤ 30 V
q
3
Current output 2: selectable in software
Function: Passive
Terminals: 33, 34; 4 ... 20 mA (0 Ω ≤ R
Source voltage 12 ≤ U
≤ 30 V
q
4a pulse output passive, terminals: 51, 52
f
5 kHz, pulse width 0.1 ... 2000 ms
max
Pos: 31.3.10 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830 @
42
2-
N
6
2
3
1
≤ 560 Ω)
B
≤ 600 Ω)
B
≤ 600 Ω)
B
CoriolisMaster FCM2000
1+
L
7
7
Setting range: 0.001 ... 1000 pulse/unit
"closed": 0 V ≤ U
"open": 16 V ≤ U
4b Pulse output active
U = 16 ... 30 V, load ≥ 150 Ω, f
5
Contact output, passive
Terminals: 41, 42
"closed": 0 V ≤ U
"open": 16 V ≤ U
6
Contact input, passive
Terminals: 81, 82
"On": 16 V ≤ U
KL
"Off": 0 V ≤ U
KL
7
Functional ground
ME22
ME23
7
MS21
≤ 2 V, 2 mA ≤ I
≤ 220 mA
CEL
CEL
≤ 30 V, 0 mA ≤ I
≤ 0.2 mA
CEH
CEH
5 kHz,
max
≤ 2 V, 2 mA ≤ I
≤ 220 mA
CEL
CEL
≤ 30 V, 0 mA ≤ I
≤ 0.2 mA
CEH
CEH
≤ 30 V
≤ 2 V
G00390
D184B111U02