Technical Data - ABB S800 I/O Manual

Fieldbus communication interface for profibus dp/dpv1
Hide thumbs Also See for S800 I/O:
Table of Contents

Advertisement

Appendix A Specifications

Technical Data

Microprocessor (CPU)
Flash PROM
Fast RAM
Power Input
Power Input Fuse
Power Consumption at 24 V d.c.
Power Dissipation
Maximum Ambient Temperature
Power Supply Monitoring Inputs
Service Port (RJ 45 connector on
TU847)
PROFIBUS (D-sub 9-pole female
socket)
ModuleBus
Power Output - ModuleBus
Switch over time at failure in a
redundant CI840 unit
3BSE020926-600
Table 26. CI840 FCI Specification
Item
Description
Motorola MCF5307 with a speed of
64 MHz
1 Mbyte
8 Mbyte
24 V d.c. (19.2 - 30)
2 AF
190 mA
7.7 W
55
C (131
F) horizontal mounted
40
C (104
F) vertical mounted
Max. input voltage: 30 V
Min. input voltage for high level: 15 V
Max. input voltage for low level: 8 V
Opto-isolated (RS-232);
19.2 Kbaud/s maximum
Opto-isolated (RS-485);
12 Mbit/s maximum
Maximum of 12 I/O modules
24 V max. = 1.4 A
5 V max. = 1.5 A
Current limited
Typical <100 ms
Maximum 150 ms
Technical Data