Section 5 Maintenance
Application Memory Reset
A CI830 can keep an application in memory for a long time, even with the power
supply disconnected. To avoid a problem with an FCI that may have an old
application, the application memory should be cleared.
To clear the application memory in CI830:
1.
2.
3.
4.
5.
6.
CI801 Firmware version
It is possible to read the firmware version from the service port (PROFIBUS
connection), at startup.
To read the firmware version:
1.
2.
3.
4.
5.
6.
3BSE020926-600
Set the address switches to 99.
Remove the power supply for a short moment.
Apply power and allow the FCI to restart. Wait for 45 seconds.
This clears the application memory.
Set the address switches to the desired station address.
Remove the power supply for a short moment.
Apply power and allow the FCI to restart. Wait for 45 seconds.
This makes the module ready for the new application.
Connect a PC to the service port of the CI801 via the service adapter (FS801
and TK802) and cable TK212/TK212A, see
Start a terminal program in the PC (for example, Hyperterminal).
Set the communication parameters to 9600 bps, 8 bits word length, no parity,
1 bit stop.
Set the station address to 0.
Disconnect power to the CI801, and connect the power again.
The LEDs, F and P, light up.
When the CI801 has started up (F LED is off after about 30 seconds), it writes
a text string on the terminal program, containing the version number (for
example,
CI801 SW 1.0/0
Figure
).
Application Memory Reset
23.