CI801 Configuration Rules
The values in brackets are in Extended HART mode and HCIR.
In order to find out if a given configuration of analog and digital modules can be
used the following method should be used:
Module
User
Type
Parameters
AI801
13
AI810
13
42
Fill in number of modules in
Calculate the sum in the three columns:
Sum User Parameters.
Sum Input Bytes.
Sum Output Bytes.
Calculate the three total sums for:
ParamSize
InSize
OutSize.
Check that:
ParamSize is less than or equal to 221 (220 if HCIR is used) in normal
mode, 218 (217 if HCIR is used) in Extended HART mode.
InSize is less than or equal to 239 in normal mode, 199 in Extended HART
mode.
OutSize is less than or equal to 112 in normal mode, 90 in Extended
HART mode.
If any of these three values is too high then the configuration can not be used.