Ci830 Fci; Address Switches; Profibus-Dp Connections - ABB S800 I/O Manual

Fieldbus communication interface for profibus dp/dpv1
Hide thumbs Also See for S800 I/O:
Table of Contents

Advertisement

Section 3 Configuration

CI830 FCI

The FCI needs to be connected to the PROFIBUS-DP and have an address selected.
It is also connected to a 24 V d.c. power source to provide power to the I/O Station.
Also refer to
estimate the fieldbus and power loading of each I/O station configuration.

Address Switches

The CI830 is equipped with two rotary switches used as station address selectors for
PROFIBUS-DP connection. The station address can be set in the range of 01 to 79.
There can be up to 32 stations per PROFIBUS-DP segment.
front panel of the CI830.
Figure 12. Front Panel of the CI830 FCI

PROFIBUS-DP Connections

The FCI connects to the PROFIBUS-DP via the 9 pin D-way connector on the front.
This allows the FCI (if not the last one at the PROFIBUS segment) to be removed
from the PROFIBUS-DP without disconnecting the other nodes of the fieldbus. 
If CI830 is the last module at a PROFIBUS segment and supplies an active
termination in the cable connector, disconnection of the power supply or the
PROFIBUS cable from CI830 can not be done without disrupting the bus.
3BSE020926-600
Configuration and Performance
SERVICE
CI830
SWX.X/Y
PROFIBUS
L+
L-
SA
on page 40 for information on how to
STN. ADDR.
5
6
Address
4
3
7
x 10
Switch #1
2
8
1
9
0
5
6
4
Address
3
7
x 1
Switch #2
2
8
1
9
0
Tx Rx
Tx
CI830 FCI
Figure 12
shows the
(Address 04
shown)
33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents