Configuration and Performance
FCI power supply connections are presented in
Configuration and Performance
CI801 Configuration Rules
The maximum number of S800 I/O stations per bus is: 99 stations
Supported communication speeds: 9.6 kbit/s to 12 Mbit/s
The maximum number of S800 I/O stations per bus segment is: 32 stations
The maximum number of I/O modules in a station is: 24 modules
The maximum number of I/O modules per cluster is: 12 modules
It is not allowed to physically install more than 12 MTUs and/or S800L modules in
a cluster.
Due to the PROFIBUS-DPV1 specification, it is not possible to always connect 24
I/O modules to one FCI. The reason is that the S800 I/O system includes more data
and user parameters than PROFIBUS-DPV1 can handle.
number of I/O modules that can be connected to one CI801.
40
Table 7. FCI Power Connection Terminal
Pin
Designation
1
L+
2
L-
3
SA
4
SB
Table
Description
+24 V d.c. Supply
0 V d.c. Supply
Redundant Power Supply Monitoring Input
Redundant Power Supply Monitoring Input
Section 3 Configuration
7.
Table 8
shows maximum
3BSE020926-600