ABB S800 I/O Manual page 46

Fieldbus communication interface for profibus dp/dpv1
Hide thumbs Also See for S800 I/O:
Table of Contents

Advertisement

CI830 Configuration Rules
In order to find out if a given configuration of analog and digital modules can be
used the following method should be used:
46
Table 10. Maximum Number of Modules on CI830 (Continued)
Module Type
AO801, AO810, AO810V2,
AO890
AO820
DP820
DP840
All DI and DO modules
ABB Standard Drive
(1) See
Table
Fill in number of modules in
Calculate the sum in the three columns:
Sum User Parameters.
Sum Input Bytes.
Sum Output Bytes.
Calculate the three total sums for:
ParamSize.
InSize.
OutSize.
Check that:
ParamSize is less than or equal to 237.
InSize is less than or equal to 244.
OutSize is less than or equal to 244.
If any of these three values is too high then the configuration can not be used.
11.
Table
11.
Section 3 Configuration
Number of Modules
13
21
11
6
24
(1)
17/24
3BSE020926-600

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents