CI840 Firmware version

CI840 Firmware version
From CI840 firmware version 3.0/0 and later, it is possible to read its firmware
version from the service port, at startup.
In a redundant pair, the firmware version can be read from the backup module. A
change over from primary state to backup state can be done by the DTM or by
disconnecting the PROFIBUS cable on the primary.
To read the firmware version:
1.
2.
3.
4.
5.

Backup/Restore Procedures

Load the CI801 Software Upgrade

Hardware Requirements
82
Connect the PC to the CI840 (TU846/TU847), using a TK212/TK212A cable
between the RS232 service port A or B on the TU846/TU847 (CI840) and the
COM1 or COM2 on the PC.
Start a terminal program in the PC (for example, Hyperterminal).
Set the communication parameters to 9600 bps, 8 bits word length, no parity, 
1 bit stop.
Disconnect the power to the CI840, and connect the power again by unlocking
the screw and locking it again.
When the CI840 has started up (after about 30 seconds), it writes a text string
on the terminal program, containing the version number (for example, 
).
CI840 SW 3.0/0
PC with WINDOWS NT 4 or later.
Service adapter (FS801 + cable TK802) 3BSE038407R1
Connection cable TK212 3BSC630167R2 or TK212A 3BSC630197R1
Section 5 Maintenance
3BSE020926-600