ABB S800 I/O Manual page 20

Fieldbus communication interface for profibus dp/dpv1
Hide thumbs Also See for S800 I/O:
Table of Contents

Advertisement

Product Scope
The FCI communicates with the PROFIBUS Master, ModuleBus Modems and the
I/O modules. The FCI handles the I/O-modules operations such as read and write
data, read status and configuration of modules and channels. The FCI has a
connector for the TB810/TB811 Optical ModuleBus Port.
The FCI provides 24 V d.c. (from the source) and an isolated 5 V d.c. power to the
base cluster's I/O modules (12 maximum) by way of the ModuleBus connections.
One power source (single or redundant 24 V d.c.) can be connected to the power
terminals (L+ & L-) of the FCI.
1:1 redundant power sources can be supervised by connecting the power sources
POWER OK status signals to terminals SA and SB.
The size, type and direction of data to be transferred on the PROFIBUS-DP bus
depends on and is determined by the I/O module type. The FCI can be configured to
send or transmit dynamic data over the PROFIBUS-DP with cycle times in the
interval from 1 ms.
Figure 4. CI830 FCI Dimensions
20
Section 1 Introduction
3BSE020926-600

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents