Device Technology; Technical Data - ABB i-bus KNX IPS/S 3.5.1 Product Manual

Ip interface secure
Table of Contents

Advertisement

ABB i-bus
®
KNX

Device technology

2
Device technology
IPS/S 3.5.1
The ABB i-bus
KNX telegrams can be sent to or received from other devices via the network.
The Interface can be used as a programming interface (ETS), and clients, e.g. Visualisations, can access
the KNX bus via the IPS/S 3.5.1.
The device uses the KNXnet/IP protocol and the KNXnet/IP Security protocol from the KNX Association
(tunneling) for communication.
The device is powered by 12 to 30 V DC or PoE (Power over Ethernet) to IEEE 802.3af class 1.
If both options are connected simultaneously, PoE will be used.
2.1

Technical data

Supply
Connections
Operating and display elements
Degree of protection
Protection class
Isolation category
IP Interface Secure IPS/S 3.5.1 connects the KNX bus to an Ethernet network.
®
Supply voltage U
Power loss
Current consumption, supply voltage
Rated voltage U
KNX current consumption
KNX
Operating voltage
LAN
Red LED and button
Green "On" LED
Yellow "LAN/Link" LED
Yellow "Telegram" LED
IP 20
II
Overvoltage category
Pollution degree
12...30 V DC (+10% / -15%)
s
or PoE (IEEE 802.3af class 1)
Maximum 1.8 W
Maximum 120 mA at 12 V
12 V DC
n
< 10 mA
Bus connection terminal
Plug-in terminal
RJ45 socket for 10/100BaseT,
IEEE 802.3 networks, AutoSensing
Assignment of the physical address
Ready indicator
Network connection indicator
KNX telegram traffic indicator
To EN 60 529
To EN 61 140
III to EN 60 664-1
2 to EN 60 664-1
IPS/S 3.5.1 | 9AKK107680A8655 EN Rev. A 11