Mitsubishi Q2ACPU User Manual page 66

Qna series melsec
Table of Contents

Advertisement

5.
I/O NUMBER ASSIGNMENT
(3)
The CPU module performs the following processing when I/O assignment is set.
1) Any of the following assignment can be performed per slot of each base unit.
Empty slot
0
16
32
48
64
2) The slots for which I/O assignment has been performed with GPP function,
the I/O assignment setting takes priority regardless of the loaded module.
• If a number of points fewer than the that of the loaded I/O module is set, the
actual number of points of the loaded I/O module is reduced.
For example, if the loaded module is a 32-point input module but I/O
assignment is set for a 16-point input module using GPP function, the latter
16 points for the input module cannot be used.
• If a number of points is greater than the that of the loaded I/O module is
set, the number of points in excess of the actual number of points is
occupied with dummy points.
• If the slot where an I/O module is loaded is set as a empty slot, the I/O
module will be unusable.
3) The slots for which I/O assignment is not performed using GPP function are
assigned with the number of points of the loaded module.
4) The slots for which I/O assignment is not performed using GPP function are
assigned I/O numbers that are consecutive to those of modules for which I/O
assignment has been performed.
Precautions
(a) If there is a disparity between the I/O assignment made in the parameter settings
and the actually loaded I/O modules, the input and output is not normally
performed.
Loaded module
Input
Output
Input/Output
Special
Assigned number of points
Input module
Output module
16
32
48
64
I/O assignment
Output
Input
Special
Input/Output
5 - 7
Special function
module
16
16
32
32
48
48
64
64
Result
No input
No output
CPU module error
CPU module error