Mitsubishi Q2ACPU User Manual page 163

Qna series melsec
Table of Contents

Advertisement

9.
MAINTENANCE FUNCTION
Diagnosis Item
Instruction code check
No END instruction
Pointer setting error
Pointer setting error
Operation error
*1
(Default
stop)
FOR-NEXT instruction
configuration error
CALL-RET instruction
configuration error
Interrupt program error
Unable to execute instruction
Extended instruction error
*1
(Default
stop)
SFC program configuration
error
SFC block configuration error
SFC step configuration error
SFC syntax error
SFC operation check error
*1
(Default
stop)
SFC program execution error
SFC block execution error
SFC step execution error
Watchdog error supervision
Program timeout
Annunciator check
CHK instruction check
Self-diagnostics list(Continued)
Diagnosis Timing
• When power is ON or RESET
• When switching from STOP to RUN
• When power is ON or RESET
• When switching from STOP to RUN
• When power is ON or RESET
• When switching from STOP to RUN
• When power is ON or RESET
• When switching from STOP to RUN
When executing each instruction
When executing each instruction
When executing each instruction
When executing each instruction
When executing each instruction
When executing each instruction
When switching from STOP to RUN
When switching from STOP to RUN
When switching from STOP to RUN
When switching from STOP to RUN
When executing each instruction
When switching from STOP to RUN
When executing each instruction
When executing each instruction
Always
Always
When executing each instruction
When executing each instruction
*1
Can be changed to operation continues by GPP function parameter setting.
*4
The detected annunciator number is displayed at ****.
*5
The detected contact and coil numbers are displayed at ***.
LED Status
CPU Module
Status
RUN
Stop
OFF
Stop
OFF
Stop
OFF
Stop
OFF
Stop/
OFF/ON
Continue
Stop
OFF
Stop
OFF
Stop
OFF
Stop
OFF
Stop/
OFF/ON
Continue
Stop
OFF
Stop
OFF
Stop
OFF
Stop
OFF
Stop/
OFF/ON
Continue
Continue
ON
Stop
OFF
Stop
OFF
Stop
OFF
Continue
ON
Continue
ON
Continue
ON
9 - 7
LED Indicator Message
(Q3A/Q4ACPU Only)
ERROR
Flickers
INSTRCT CODE ERR.
Flickers
MISSING END INS.
Flickers
CAN'T SET(P)
Flickers
CAN'T SET(I)
Flickering/
OPERATION ERROR
ON
Flickers
FOR-NEXT ERROR
Flickers
CAN'T EXECUTE(P)
Flickers
CAN'T EXECUTE(I)
Flickers
INST.FORMAT ERR.
Flickering/
EXTEND INST.ERR.
ON
Flickers
SFCP.CODE ERROR
Flickers
CAN'T SET(BL)
Flickers
CAN'T SET(S)
Flickers
SFCP.FORMAT ERR.
Flickering/
SFCP.OPE.ERROR
ON
ON
SFCP.EXE.ERROR
Flickers
BLOCK EXE.ERROR
Flickers
STEP EXE.ERROR
Flickers
WDT ERROR
ON
PRG.TIME OVER
*4
OFF
F****
<CHK>ERR
OFF
–5
***-***

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q3acpuQ4acpuQ2acpus1

Table of Contents