16. POWER SUPPLY MODULE
(5)
Setting
On the A61P(EU), A62P(EU), A65P or A66P power supply module, the input voltage
select terminals must be short-circuited by a jumper (accessory). The following
explains the way of setting.
POINT
If the setting differs from the supply power voltage, the following occurs. Be sure
to set it correctly.
Set to 100VAC
(jumper fitted as
indicated at (2))
Set to 200VAC
(jumper fitted as
indicated at (3))
No setting
(jumper not fitted)
Supply Power Voltage
100VAC
No fault occurs in the module.
However, the CPU module does not
operate.
No fault occurs in the module.
However, the CPU module does not operate.
16 - 14
200VAC
The power supply module is
damaged.
(The CPU module is
not damaged.)