5.
I/O NUMBER ASSIGNMENT
The setting details are as follows:
Item
Slot setting
Type
Points
Start XY
Model name
Base specification
Power model name
Extension cable
Setting
Set data for each slot.
(Not necessary to set all data).
Set the module type.
Set the number of points for the module.
Set the start number of XY devices of the module.
Set the model name of the module.
Set data for each base unit.
Set the model name of the power supply module.
Set the model name of the extension cable.
The items without settings are handled as follows:
Type and Points : In accordance with the loaded module.
Start XY
: The number following the total points obtained by adding the
number of points of the modules already set.
If there is any duplication, an error (SP.UNIT LAY ERROR) is
detected.
POINT
The power supply module names set in the base specification is only used for the
current capacity check in the PLC diagnostics mode and not used for a CPU
module. Therefore, even if they are not set, any problem does not occur.
Setting range
Free/input/output/special
0 to 64 points
(in 16 point units)
0 to 1FFF (in 16 point units)
Up to 16 characters
Up to 16 characters
Up to 16 characters
5 - 6
Default value
No setting
No setting