17.3.3 Sensor test

Operating line 163 can be used to check the connected sensors; if available, the
current setpoints and limit values are displayed on operating line 164.
The 11 temperatures can be queried by entering 0...11:
Input
Op. line 163 (actual values)
0
Actual value of outside sensor at
terminal B9.
If the outside temperature is ob-
tained via data bus, the display
shows ---
1
Actual value of flow sensor of
heating circuit 1 at terminal B1
2
Actual value of room sensor of
heating circuit 1 at terminal B5
Actual value of room unit sensor
3
of heating circuit 1 at terminal A6
Actual value of return sensor at
4
terminal B7.
If the return temperature is ob-
tained via data bus, the display
shows ---
Actual value of storage tank sen-
5
sor at terminal B31
6
Actual value of storage tank sen-
sor at terminal B32
7
Actual value of collector sensor at
terminal B6
Actual value of boiler sensor at
8
terminal B2
Actual value of flow sensor of
9
heating circuit 2 at terminal B12
Actual value of room sensor of
10
heating circuit 2 at terminal B52
Actual value of room unit sensor
11
of heating circuit 2 at terminal A6
Errors in the measuring circuits are displayed as follows:
= short-circuit (thermostat: contact closed)
– – – = interruption (thermostat: contact open)
When changing from operating line 163 to 164, and vice versa, the selected sensor
(setting 0...11) is maintained.
Basic Documentation RVP360
17 Function block: Service functions and general settings
Op. line 164 (setpoints)
No display
Flow temperature setpoint for
heating circuit 1. If there is no
heat request, the display shows
---
Setpoint for room temperature of
heating circuit 1
Setpoint for room temperature of
heating circuit 1
Limit value return temperature.
If no return temperature limitation
is used, the display shows ---
D.h.w. temperature setpoint
D.h.w. temperature setpoint
Setpoint for collector sensor (cor-
responds to the actual value of
storage tank sensor B32 plus
temperature differential solar ON
on operating line 201)
Boiler temperature setpoint
(switch-off point).
If there is no heat request, the
display shows ---
Setpoint for flow temperature of
heating circuit 2.
If there is no heat request, the
display shows ---
Setpoint for room temperature of
heating circuit 2
Setpoint for room temperature of
heating circuit 2
75/106
CE1P2546en
2017-07-24