Manual D.h.w. Charging - Siemens RVP360 Basic Documentation

Heating controller for 2 heating circuits and d.h.w.
Table of Contents

Advertisement

Siemens
Building Technologies

14.14 Manual d.h.w. charging

D.h.w. charging can be started manually by pressing the d.h.w. button
seconds. For confirmation, the button flashes for 5 seconds.
Manual d.h.w. charging is also active when ...
d.h.w. heating is not released,
the d.h.w. temperature lies inside the switching differential,
d.h.w. heating is switched off,
d.h.w. heating is switched off due to the holiday period,
d.h.w. heating is locked because the maximum charging time has been
exceeded.
Manually started charging is aborted only if the d.h.w. temperature setpoint is
reached or if the maximum charging time has been exceeded.
After manual charging, d.h.w. heating always remains on, irrespective of whether or
not it was switched on before the manual charging.
If d.h.w. heating shall be switched off again after manual charging, the button must
be pressed again after it flashes (button extinguishes).
Manual charging is not possible when heating the d.h.w. with an electric immersion
heater.
Basic Documentation RVP360
14 Function block: D.h.w.
for 5
65/106
CE1P2546en
2017-07-24

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents