Relay Test; Sensor Test - Siemens RVL471 Basic Documentation

Heating and domestic hot water controller
Table of Contents

Advertisement

Siemens Building Technologies
HVAC Products
25.3.2

Relay test

The eight output relays can be individually energized. Depending on the type of plant,
the following codings apply:
Input
Plants with a valve (plant types
1–x, 3–x, 4–x, and 6–x)
0
Normal operation
1
All contacts open
2
Heating circuit valve OPEN (Y1)
3
Heating circuit valve CLOSED (Y2)
4
Heating circuit pump / circulating
pump ON (M1)
5
Charging pump / diverting valve ON
(M3/Y3)
6
Circulating pump ON (M4)
7
Multifunctional relay energized (K6)
8
D.h.w. valve OPEN (Y7)
9
D.h.w. valve CLOSED (Y8)
There are 4 choices to terminate the relay test:
• Entry of 0 on the operating line
• Leaving the setting level by pressing button
• Leaving the setting level by pressing the Info button or any of the operating mode but-
tons
• Automatically after 30 minutes
25.3.3

Sensor test

The connected sensors can be checked on operating line 163. In addition, if available,
the current setpoints and limit values are displayed.
On the display, the current setpoints are identified by SET, the actual values by
ACTUAL (also refer to section "28 Handling")
The 9 temperatures can be called up by entering 0...8:
Input
Display SET
0
No display
1
Setpoint of flow / boiler temperature.
With the plant types using a boiler, the
switch-off point is displayed. If there is
no demand for heat, the display shows
---
2
Setpoint of room temperature.
With the plant types with no heating
circuit, the display shows ---
3
Setpoint of room temperature.
With the plant types with no rooms,
the display shows ---
Basic Documentation RVL471
25 Function block "Service functions and general settings"
Plants with a burner (plant types
2–x, and 5–x)
Normal operation
All contacts open
Burner stage 1 ON (K4)
Burner stages 1 and 2 ON
Heating circuit pump / circulating
pump ON (M1)
Charging pump / diverting valve ON
(M3/Y3)
Circulating pump ON (M4)
Multifunctional relay energized (K6)
D.h.w. valve OPEN (Y7)
D.h.w. valve CLOSED (Y8)
or
Display ACTUAL
Actual value of outside sensor at
terminal B9.
If the outside temperature is deliv-
ered via the data bus, the display
shows ---
Actual value of flow / boiler tem-
perature sensor at terminal B1
Actual value of room temperature
sensor at terminal B5
Actual value of room unit sensor at
terminal A6
87/118
CE1P2524E
23.10.2002