Building Technologies
9.6

Heating curve

9.6.1

Purpose

With space heating systems, flow temperature control is always weather-
compensated. The heating curve assigns the flow temperature setpoint to the pre-
vailing outside temperature.
9.6.2

Settings

The heating curve settings are made via 2 operating lines.
The following settings are required:
Flow temperature setpoint at an outside temperature of 5 °C
Flow temperature setpoint at an outside temperature of 15 °C
The basic settings during the commissioning phase are made based on the plan-
ning documentation or according to local practices.
They are made on operating lines 14 and 15.
Op. line
Setpoint
14
Flow temperature setpoint at an outside temperature of 15 °C
15
Flow temperature setpoint at an outside temperature of -5 °C
T
Vw
120
110
100
90
80
70
60
50
40
30
20
10
20
15
10
5
BZ 14
Heating curve diagram showing the basic settings
BZ 14
Setting operating line 14, flow temperature setpoint at an outside temperature of 15 °C
BZ 15
Setting operating line 15, flow temperature setpoint at an outside temperature of -5 °C
T
Outside temperature
A
T
Flow temperature setpoint
Vw
Basic Documentation RVP360
9 Function block: Space heating
0
-5
-10 -15 -20
-30
BZ 15
T
A
CE1P2546en
2017-07-24