14.5.3 D.h.w. heating during holiday periods
In holiday mode, d.h.w. heating is provided as follows:
Op. line
Op. line
D.h.w. heating
121
123
0
0, 1 or 2 No d.h.w. heating when own controller operates in holiday
mode
1
0, 1 or 2 No d.h.w. heating when all controllers in the same segment
operate in holiday mode
2
0, 1 or 2 No d.h.w. heating when all controllers in the interconnected
system operate in holiday mode
14.6

Priority and flow temperature setpoint

14.6.1 Settings

Op. line
D.h.w. priority
124
0
Absolute
1
Shifting
2
Shifting
3
None (parallel)
4
None (parallel)
Basic Documentation RVP360
14 Function block: D.h.w.
Oper.
Heating program,
mode
optim., holidays
06:00...18:00, no op-
timization
07:00...23:00
07:00...22:00, opti-
mized switching on
produces a forward
shift of 2 hours
03:00...22:00, holi-
days
Oper.
Heating program,
mode
optim., holidays
06:00...18:00, no op-
timization
08:00...23:00
07:00...22:00, opti-
mized switching on
produces a forward
shift of 2 hours
05:00...21:00
Flow temperature
setpoint according to ...
d.h.w.
d.h.w.
maximum selection
d.h.w.
maximum selection
Release
D.h.w. heating is
released from
04:00 to 23:00
Release
D.h.w. heating is
released from
04:00 to 23:00
59/106
CE1P2546en
2017-07-24