Caution
Siemens Building Technologies
HVAC Products
18
Function block Test and display
18.1
Operating lines
Line
Function, parameter
141
Sensor test
142
Relay test
143
Display of active limitations
145
Address and identification of device at terminal A6
146
Contact status at terminal H5
149
Reset of operating lines 61...123 (heating engineer level)
150
Software version
18.2
Mode of operation
18.2.1 Sensor test
All temperature values measured can be displayed on operating line 141:
Code Sensor or unit
0
Outside sensor (terminal B9)
1
Flow temperature sensor (terminal B1)
2
D.h.w. temperature sensor (terminal B3)
3
Room unit sensor (terminal A6)
4
Primary return temperature sensor (terminal B7)
5
Multipurpose sensor (terminal B71)
Faults in the measuring circuits are indicated as follows:
--- = open-circuit or no sensor connected
ooo = short-circuit
18.2.2 Relay test
All relays can be manually energized on operating line 142, allowing their states to be
checked:
Code
Response or current status
0
Normal operation (no test)
1
All relay contacts open
2
Relay contact at terminal Y1 closed
3
Relay contact at terminal Y2 closed
4
Relay contact at terminal Q1 closed
5
Relay contact at terminal Q3 / Y7 closed
6
Relay contact at terminal Y5 closed
7
Relay contact at terminal Y6 closed
8
Relay contact at terminal Q7 / Y8 closed
To terminate the relay test:
• Select another operating line
• Press one of the operating mode buttons
• Automatically after 8 minutes
With plant type no. 5, the relay test may be made only when the main shutoff valve is
fully closed!
Recommendation: When making the relay test, always close the main shutoff valve.
Basic Documentation RVD110, RVD130
18 Function block Test and display
Unit
Factory setting
0
0
RVD110: 0...5
RVD130: 0...8
Display function
Display function
Display function
Display function
CE1P2381E
Range
0...5
0 / 1
61/94
27.05.2004