Note on the operating
line tables
24/106
Siemens
Building Technologies
5
Function block: End-user space heating
This function block provides settings that the end-user himself can make.
5.1
Operating lines
Line
Function, parameter
1
Room temperature setpoint for NORMAL heating
2
Room temperature setpoint for REDUCED heating
3
Room temperature setpoint for
holiday/protection mode
4
Weekday, for entering the heating program
5
1. 1st heating phase, start of NORMAL heating
6
1. 1st heating phase, end of NORMAL heating
7
2. 2nd heating phase, start of NORMAL heating
8
2. 2nd heating phase, end of NORMAL heating
9
3. 3rd heating phase, start of NORMAL heating
10
3. 3rd heating phase, end of NORMAL heating
12
Date of first day
13
Date of last day
14
Heating curve, flow temperature setpoint at an outside
temperature of 15 °C
15
Heating curve, flow temperature setpoint at an outside
temperature of -5 °C
In column "Heating circuit" it is indicated for each operating line which heating cir-
cuit can be set and how the setting affects the heating circuits. Meaning:
1
= settings only apply to heating circuit 1
2
= settings only apply to heating circuit 2
1, 2 = settings must be made separately for both heating circuits
1+2 = settings apply to both heating circuits
–
= settings or function are independent of the heating circuits
5.2
Setpoints
5.2.1
General
The setpoints for the NORMAL and the REDUCED room temperature and for holi-
day/protection mode are entered directly in °C room temperature. They are inde-
pendent of whether or not the control uses a room sensor.
5.2.2
Frost protection for the building
The lowest valid room temperature setpoint always corresponds to at least the
setpoint for holiday/protection mode (setting on operating line 3), even if lower
setpoints for the NORMAL and the REDUCED room temperature have been en-
tered (settings on operating lines 1 and 2).
If a room sensor is used and the room temperature falls below the setpoint for holi-
day/protection mode, the automatic ECO function – if available – aborts the OFF
mode until the room temperature has risen 1 °C above the setpoint for holi-
day/protection mode.
Basic Documentation RVP360
5 Function block: End-user space heating
Factory setting
Unit
(range)
20.0 (0...35)
°C
14.0 (0...35)
°C
10.0 (0...35)
°C
1-7 (1...7 / 1-7)
-
06:00 (00:00...24:00)
hh:mm
22:00 (00:00...24:00)
hh:mm
--:-- (00:00...24:00)
hh:mm
--:-- (00:00...24:00)
hh:mm
--:-- (00:00...24:00)
hh:mm
--:-- (00:00...24:00)
hh:mm
--.-- (01.01...31.12)
dd:mm
--.-- (01.01...31.12)
dd:mm
30 (20...70)
°C
60 (20...120)
°C
Heating
circuit
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
CE1P2546en
2017-07-24