Heating During The Holiday Period - Siemens RVL471 Basic Documentation

Heating and domestic hot water controller
Table of Contents

Advertisement

Example 1
Example 2
68/118
Siemens Building Technologies
HVAC Products
With setting 1, d.h.w release depends on the setting made on operating line 121. In an
interconnected system of several controllers, that is, in the case of several heating
programs, the circulating pump runs if at least one of the connected controllers pro-
vides heating to the NORMAL temperature according to its heating program (independ-
ent of the operating mode), and is not in holiday mode.
Release of d.h.w. heating is shifted forward in time by one hour against the times of the
heating program. If optimum start control is active, the optimized switch-on times are
used - and not the times entered.
With plant types 4–x, 5–x, and 6–x, and the setting of "0" (own controller) on operating
line 121, d.h.w. heating will never be released since these plant types have no own
heating program.
The release of d.h.w. heating is explained using 2 examples, in which controllers A, B,
C and D are interconnected via the data bus:
Operating
Operating
line 121
line 123
2
1
Operating
Operating
line 121
line 123
1
2
17.2.3
D.h.w heating during the holiday period
In holiday mode, d.h.w. heating is provided as follows:
Operating
Operating
line 121
line 123
0
0, 1, or 2
1
0, 1, or 2
2
0, 1, or 2
Basic Documentation RVL471
17 Function block "Release of d.h.w. heating"
Con-
Operat-
Heating program, opti-
trollers
ing mode
mization, holidays
A
06:00...18:00, no optimi-
zation
B
07:00...23:00
C
07:00...22:00, optimum
start control shifts forward
by 2 hours
D
03:00...22:00, HOLIDAYS
Con-
Operat-
Heating program, opti-
trollers
ing mode
mization, holidays
A
06:00...18:00, no optimi-
zation
B
08:00...23:00
C
07:00...22:00, optimum
start control shifts forward
by 2 hours
D
05:00...21:00
D.h.w. heating
No d.h.w. heating when own controller is in holiday mode
No d.h.w. heating when all controllers in the same seg-
ment are in holiday mode
No d.h.w. heating when all controllers in the intercon-
nected system are in holiday mode
Release
D.h.w. heating is
released from
04:00 to 23:00
Release
D.h.w. heating is
released from
04:00 to 23:00
CE1P2524E
23.10.2002