Power Connections For Units With A Width Of 135 Mm And 180 Mm - Siemens SIMOVERT MASTERDRIVES Operating Instructions Manual

Motion control, frequency inverter dc-ac compact plus type
Hide thumbs Also See for SIMOVERT MASTERDRIVES:
Table of Contents

Advertisement

Connecting-up
7.1.2

Power connections for units with a width of 135 mm and 180 mm

X3 - DC link bus
module
X2 – Motor
connection
PE
U2
V2
W2
7-6
The DC link bus module serves to supply the unit with electrical energy.
Bar
Designation
3
PE3
2
D / L-
1
C / L+
Connectable cross-section: "Electro-plated copper" 3x10 mm, rounded
off according to DIN 46433
Bar 1 is at the front when installed.
Table 7-3
DC link busbars
The motor connection is to a terminal block at the bottom of the unit.
Terminal
PE
Protective conductor connection
U2 / T1
V2 / T2
W2 / T3
Connectable cross-section:
Housing width 135 mm: 10 mm² (AWG 8), stranded
Housing width 180 mm: 16 mm² (AWG 6), stranded
Viewed from the front, Terminal PE is at the left.
Table 7-4
Motor connection
Meaning
Protective conductor connection
DC link voltge -
DC link voltage +
Meaning
Phase U2 / T1
Phase V2 / T2
Phase W2 / T3
Operating Instructions
10.99
Range
DC 510 - 650 V
DC 510 - 650 V
Range
3AC 380 - 480 V
3AC 380 - 480 V
3AC 380 - 480 V
3AC 380 - 480 V
6SE7087-6KP50
Siemens AG
SIMOVERT MASTERDRIVES

Hide quick links: