Parameterization
NOTE
8-8
Some parameters may also be displayed without a parameter number,
e.g. during quick parameterization or if "Fixed setting" is selected. In
this case, parameterization is carried out via various sub-menus.
Example of how to proceed for a parameter reset.
É
Ë
P
0.0 A
0 V
00
MotionControl
#
0.00 min-1
*Menu selection
*
0.00 min-1
OP: Upread
Ready
OP: Download
Selection of fixed setting
Ë
É
Ë
P
Fixed Setting
Fixed Setting
*Select FactSet
*Select FactSet
FactSet.
#FactSet.
Selection of factory setting
wait
Ë
É
Ë
P
Factory Setting
Menu Selection
#FactSet.
*User Param..
*No FactSet
Param. Menu..
busy............
FixedSet...
Start of factory setting
It is not possible to start the parameter reset in the "Run" status.
2 x
É
Ë
É
P
Menu Selection
*User Param.
Param Menu..
Fixed Set...
É
Ë
É
P
Factory Setting
FactSet.
*No FactSet
6SE7087-6KP50
Operating Instructions
SIMOVERT MASTERDRIVES
10.99
Ë
Menu Selection
*User Param.
Param Menu..
#Fixed Set...
Ë
Factory Setting
#FactSet.
*No FactSet