Electronic Power Supply With 18 V Dc Infeed (Option K72); Electronic Power Supply With 24 V Dc Infeed (Option K73); Electronic Power Supply With 1 Ac 230 V Infeed (Option K74); Cabinet Lighting In The Control Section (Option L50) - Siemens SINAMICS SL150 6SL39616RC100AA02 Operating Instructions & Installation Instructions

Medium-voltage
Table of Contents

Advertisement

Description
3.2 Options
● 1 IM151-1 interface module (6ES7151-1AA05-0AB0)
● 1 PM-E Power Module (6ES7138-4CA01-0AA0)
3.2.12

Electronic power supply with 18 V DC infeed (option K72)

The infeed for the electronic components can be 18 V DC (24 V DC +/- 25 %).
3.2.13

Electronic power supply with 24 V DC infeed (option K73)

The infeed for the electronic components can be 24 V DC +/- 15 %.
3.2.14

Electronic power supply with 1 AC 230 V infeed (option K74)

The infeed for the electronic current opponents can be
1AC 100-120 V / 220-240 V (-15 % +10 %).
3.2.15

Cabinet lighting in the control section (option L50)

The cabinet lighting is automatically switched on using an integrated motion detector. If the light
is switched on by the motion detector, it stays on for three minutes.
3.2.16

Cabinet anti-condensation heating for the power unit (option L55)

The anti-condensation heating is used at low ambient temperatures and high levels of humidity
to prevent condensation from forming. The heating is controlled via a thermostat. The heating
is externally supplied with power.
3.2.17

Dust protection (option M11)

To prevent dangerous dust deposits from accumulating in the power unit components,
additional filter mats are attached to the outside of the device.
A differential pressure technique continually determines the amount of dust in the filter mats.
When the differential pressure switch responds, a fault message is output and the converter is
switched off.