10.99
Derating curves
Siemens AG
6SE7087-6KP50
SIMOVERT MASTERDRIVES
Permissible rated input voltage in %
according to VDE 0110 / IEC 664-1
(not required by UL / CSA)
100
75
50
0
1000
Height above sea level in m
Permissible rated current in %
100
90
80
70
60
0
1000
Height above sea level in m
Permissible rated current in %
100
75
50
25
0
0
10
20
Coolant temperature in °C
Fig. 11-1
Derating curves
Operating Instructions
2000
3000
4000
2000
3000
4000
30
40
50
Technical Data
Height
Derating
[m]
factor K
1
1000
1.0
2000
0.9
3000
0.845
4000
0.8
Temp
Derating
[°C]
factor K
2
50
0.879
45
1.0
40
1.125
35
1.25 *
30
1.375 *
25
1.5 *
*See note
below
11-5