6.3.2
Removal and installation of the drain cup
1
2
5
4
3
1. Remove overflow hose from the connector on the water cup.
2. Remove grounding cable from the grounding lance.
3. Release the hose clamp, then remove water drain hose from the con­
nector on the water cup.
4. Undo the two screws fixing the drain cup to the unit using a screwdriver,
then remove the drain cup downwards.
5. Undo the screw, then remove grounding lance.
Installation of the drain cup follows the reverse sequence.
Important: reattach grounding cable to grounding lance.
51