5.4.8

Water management settings

Select "Water Manag." in the settings menu, then press the <Set> key.
Settings
Power Limit :Set
On/Off Timer :Set
Water Manag.:Set
Date
:11-08-31
Time
:12:00
Esc
The water management settings appear. Press the < > and < > keys in order to select the individual
settings. Detailed information on the different settings are found in the following chapters.
5.4.8.1

Selecting the conductivity range of the supply water

Select "Conductivity" in the water management settings submenu, then press the <Set> key.
Settings
Power Limit :Set
On/Off Timer :Set
Water Manag.:Set
Date
:11-08-31
Time
:12:00
Esc
In the upcoming modification dialogue select the conductivity range of the supply water.
Factory setting:
Options:
5.4.8.2

Setting the drain factor

Select "Drain Factor" in the water management settings submenu, then press the <Set> key.
Settings
Power Limit :Set
On/Off Timer :Set
Water Manag.:Set
Date
:11-08-31
Time
:12:00
Esc
In the upcoming modification dialogue set the drain factor in relation to the steam capacity.
Factory setting:
Setting range:
Water Manag.
Conductivity:>125µS
Drain Factor:1.0
Idle Operat.:Set
Force Drain :On
Force Delay :72h
Set
Esc
Set
Water Manag.
Conductivity:>125µS
Drain Factor:1.0
Idle Operat.:Set
Force Drain :On
Force Delay :72h
Set
Esc
Set
>125 μS/cm
>125 μS/cm, <125 μS/cm
Water Manag.
Conductivity:>125µS
Drain Factor:1.0
Idle Operat.:Set
Force Drain :On
Force Delay :72h
Set
Esc
Set
1.0
0.5...2.0
Conductivity
>125µS
>125µS
<125µS
Esc
Set
Drain Factor
1.0
1.0
Esc
Set
33