5.4.3.9

Selecting the supply air limitation signal

Note: This setting is available only if the external controller or the internal P or PI controller and the
supply air limitation are activated.
Select "Limitsignal" in the control settings menu, then press the <Set> key.
Settings
Language
:English
Controls
:Set
Cylinder
:6564
SC-System
:Set
Power Limit :Set
Esc
In the upcoming modification dialogue select the desired supply air limitation signal.
Factory setting:
Options:
5.4.3.10 Setting the lower limit value for the supply air limitation
Note: This setting is available only if the external controller or the internal P or PI controller and the
supply air limitation are activated.
Select "Limit Min" in the control settings menu, then press the <Set> key.
Settings
Language
:English
Controls
:Set
Cylinder
:6564
SC-System
:Set
Power Limit :Set
Esc
In the upcoming modification dialogue set the lower limit value in %rH for the supply air limitation.
Factory setting:
Options:

5.4.3.11 Setting the upper limit value for the supply air limitation

Note: This setting is available only if the external controller or the internal P or PI controller and the
supply air limitation are activated.
Select "Limit Max" in the control settings menu, then press the <Set> key.
Settings
Language
:English
Controls
:Set
Cylinder
:6564
SC-System
:Set
Power Limit :Set
Esc
In the upcoming modification dialogue set the upper limit value in %rH for the supply air limitation.
Factory setting:
Setting range:
28
Controls
Integr.-Time:8min
Lim. Control:On
Limitsignal :0-10V
Limit Min
:70%rH
Limit Max
:90%rH
Set
Esc
Set
0–10V
0–5V, 1–5V, 0–10V, 2–10V, 0–16V, 3.2–16V, 0–20mA, 4–20mA
Controls
Integr.-Time:8min
Lim. Control:On
Limitsignal :0-10V
Limit Min
:70%rH
Limit Max
:90%rH
Set
Esc
Set
70 %rH
15 ... 95 %rH
Controls
Integr.-Time:8min
Lim. Control:On
Limitsignal :0-10V
Limit Min
:70%rH
Limit Max
:90%rH
Set
Esc
Set
90 %rH
15 ... 95 %rH
Limitsignal
0-10V
0-5VPoti
1-5V
0-10V
2-10V
Esc
Set
0-16V
3.2-16V
0-20mA
4-20mA
Limit.Min
70 %rH
70 %rH
Esc
Set
Limit Max
90 %rH
90 %rH
Esc
Set