50
Installation of the steam cylinder follows the reverse sequence. Observe
the following:
Before installing the steam cylinder in the unit, check the O­ring of the
cylinder receptacle for damage and replace if necessary.
Moisten the O­ring of the cylinder receptacle with water (do not use
grease or oil), then insert steam cylinder into the socket and push it
down to the stop.
Attach the electrode plugs and the level sensor plug to the respective
electrode and sensor connections in accordance with colour code (see
table below).
532A / 534A
832A / 834A
1532A / 1534A
red
sensor
white
brown
sensor
white
Fasten steam hose on the connector of the steam cylinder with hose
clamps.
CAUTION!
A leaky steam hose can cause damage due to moisture inside the
unit.
The outlet connector of the steam cylinder is made of plastic. Do
not overtighten the hose clamp on the steam connector of the
steam cylinder.
Steam cylinder type
2362A / 2364A
3262A / 3264A
black
brown
red
black
brown
sensor
white
4564A / 6564A
black
red
red
brown
black
sensor
white
brown
red
black