If the timer is activated, up to eight switching points (events 1 8) with different humidity setpoints
can be defined. Each switching point is defined by a weekday or weekday range, the switching point
and the humidity setpoint.
Configuration notes:
–
the settings of an event remain active up to the next event.
–
the software does not check the plausibility of the timer settings. Therefore, make sure your
settings make sense.
–
the On/Off timer (see chapter 5.4.7) overrides the humidity setpoint timer.
5.4.3.6
Setting the proportional range for the internal P/PI controller
Note: This menu item is available only if the internal P or PI controller is activated.
Select "P-Band" in the control settings menu, then press the <Set> key.
Settings
Controls
Language
:English
Controlsign.:0-10V
Controls
:Set
Setpoint
Cylinder
:6564
P-Band
SC-System
:Set
Integr.-Time:8min
Power Limit :Set
Lim. Control:Off
Esc
Set
In the upcoming modification dialogue set the proportional range in %rh for the internal P/PI controller.
Factory setting:
18 %rh
Setting range:
6...65 %rh
5.4.3.7
Setting the integral time for the internal PI controller
Note: This setting is available only if the internal PI controller is activated.
Select "Integr.-Time" in the control settings menu, then press the <Set> key.
Settings
Controls
Language
:English
Controlsign.:0-10V
Controls
:Set
Setpoint
Cylinder
:6564
P-Band
SC-System
:Set
Integr.-Time:8min
Power Limit :Set
Lim. Control:Off
Esc
Set
In the upcoming modification dialogue set the integral time in minutes for the internal PI controller.
Factory setting:
8 minutes
Setting range:
1...60 minutes
5.4.3.8
Activating/Deactivating the supply air limitation
Note: This setting is available only if the control type is set to "External", "Int. (P)" or "Int. (PI)".
Select "Lim. Control" in the control settings menu, then press the <Set> key.
Settings
Controls
Language
:English
P-Band
Controls
:Set
Integr.-Time:8min
Cylinder
:6564
Lim. Control:On
SC-System
:Set
Limitsignal :0-10V
Power Limit :Set
Limit Min
Esc
Set
In the upcoming modification dialogue activate or deactivate the supply air limitation (Signal Z).
Factory setting:
Off
Options:
On, Off
P-Band
:Set
18 %rH
:18%rH
Esc
Set
Esc
Integr.-Time
:Set
8 min
:18%rH
Esc
Set
Esc
Lim. Control
:18%rH
Off
On
:70%rH
Esc
Set
Esc
18 %rH
Set
8 min
Set
On
Set
27