5.4.3.1
Selecting the signal source
Select "SignalSource" in the control settings menu, then press the <Set> key.
Settings
Controls
Language
:English
SignalSource:Analog
Controls
:Set
Hum.Control :Int.(PI)
Cylinder
:6564
Controlsign.:0-10V
SC-System
:Set
Setpoint
Power Limit :Set
P-Band
Esc
Set
Esc
In the upcoming modification dialogue select the desired signal source.
Factory setting:
Analog
Options:
Analog (internal or external controller), Modbus
5.4.3.2
Selecting the regulation mode
Select "Hum.Control" in the control settings menu, then press the <Set> key.
Settings
Controls
Language
:English
SignalSource:Analog
Controls
:Set
Hum.Control :Int.(PI)
Cylinder
:6564
Controlsign.:0-10V
SC-System
:Set
Setpoint
Power Limit :Set
P-Band
Esc
Set
Esc
In the upcoming modification dialogue select the desired regulation mode.
Factory setting:
External
Options:
External (external continuous controller)
24VOn/Off (external On/Off humidistat)
Int. (P) (Internal P controller)
Int. (PI) (Internal PI controller)
5.4.3.3
Selecting the control signal
Note: This setting is available only if the signal source is set to "Analog" and the control type is set to
"External", "Int. (P)" or "Int. (PI)".
Select "Controlsign." in the control settings menu, then press the <Set> key.
Settings
Controls
Language
:English
SignalSource:Analog
Controls
:Set
Hum.Control :Int.(PI)
Cylinder
:6564
Controlsign.:0-10V
SC-System
:Set
Setpoint
Power Limit :Set
P-Band
Esc
Set
Esc
In the upcoming modification dialogue select the desired control signal.
Factory setting:
0–10V
Options:
0–5VPoti, 1–5V, 0–10V, 2–10V, 0–16V, 3.2–16V, 0–20mA, 4–20mA
SignalSource
Analog
Analog
Modbus
:Set
:18%rH
Set
Esc
Hum.Control
External
External
24VOnOff
:Set
Int.(P)
:18%rH
Int.(PI)
Set
Esc
Controlsign.
0-10V
0-5VPoti
1-5V
:Set
0-10V
:18%rH
2-10V
Set
Esc
0-16V
3.2-16V
0-20mA
4-20mA
Set
Set
Set