5.4

Unit settings

5.4.1

Launching the unit settings menu

Select the unit settings menu:
Path: Main menu > User > Password entry: 3562 > Settings
AT4 130kg/h 400V3
Standby
2011-08-31 12.00.00
Menu
press the < > and < > keys in order to select the individual settings or settings submenus. Detailed
information on the different settings are found in the following chapters.
5.4.2

Selecting the dialogue language

Select "Language" in the unit settings menu, then press the <Set> key.
Settings
Language
:English
Controls
:Set
Cylinder
:6564
SC-System
:Set
Power Limit :Set
Esc
In the upcoming modification dialogue select the desired dialogue language. After confirmation, the unit
automatically switches to the selected dialogue language.
Factory setting:
Options:
5.4.3

Control settings

Select "Controls" in the unit settings menu, then press the <Set> key.
Settings
Language
:English
Controls
:Set
Cylinder
:6564
SC-System
:Set
Power Limit :Set
Esc
The display with control settings appears. The settings available depend on the selected signal source,
the regulation mode and the modulation mode. The display above shows the maximum number of set­
tings available. Please refer to the following chapters for further information on the individual control
settings.
24
Main Menu
User
:Set
Engineering :Set
Diagnostic
:Set
Esc
Set
User Code
3562
Enter Number
Confirm with Set
Esc
Set
Language
English
English
German
French
Italian
Set
Esc
Set
country specific
diverse languages
Controls
SignalSource:Analog
Hum.Control :Int.(PI)
Controlsign.:0-10V
Setpoint
:Set
P-Band
:18%rH
Set
Esc
Set
Integr.-Time:8min
Lim. Control:On
Limitsignal :0-10V
Limit Min
:70%rH
Limit Max
:90%rH
User
Settings
Maintenance :Set
Language
Settings
:Set
Controls
Modbus
:Set
Cylinder
SC-System
Power Limit :Set
Esc
Set
Esc
On/Off Timer :Set
Water Manag.:Set
Date
Time
Contrast
:English
:Set
:6564
:Set
Set
:11-08-31
:12:00
:15