PROFIBUS DP Communication Module

8.9.8 Module Status

Definition
Module status structure
8-32
The module status reflects the status of the configured module (here: soft
starter) and represents a specification of the code-related diagnosis. The module
status starts after the code-related diagnosis and comprises 5 bytes.
The structure of the module status is as follows:
7 6 5
Byte 8
0 0 0 0 0 1 0 1
7
Byte 9
82
7
Byte 10
0
Byte 11
0
7 6 5
4
Byte 12
0
0
Figure 8-17:Structure of the module status
0
Bit number
= 0x05
Length of the module status
including byte 8 (=5 bytes)
Code for module status
0
H
0
Not relevant
H
Not relevant
H
3 2 1 0
Bit number
0
x
00
: Soft starter OK; valid user data
B
01
: Soft starter error; invalid user data
B
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04