PROFIBUS DP Communication Module
ID
Bit
Byte
No.:
3
327
2
Therm. motor model overload
4
328
2
Overload switch-off
5
329
2
Idle time active
6
330
2
Cool-down time active
7
2
Reserved = 0
0-6
3
Reserved = 0
7
352
3
Control input
0
340
4
Asymmetry recognized
1
341
4
Asymmetry switch-off
2
334
4
Current limit exceeded
3
335
4
Current limit undershot
4
336
4
Current limit switch-off
5
4
Reserved = 0
6
4
Reserved = 0
7
339
4
Motor stalled - switched off
0
344
5
Input 1
1
345
5
Input 2
2
346
5
Input 3
3
347
5
Input 4
4-7
5
Reserved = 0
0
342
6
Ground fault
1
343
6
Ground fault switch-off
8-50
Signal bit
E
Meaning/Acknowledgment
*)
No.
E4
Overload recognized, the signal bit is updated
continuously.
E24
The motor is switched off due to a recognized overload.
The signal bit is deleted when the cause for the switch-off
has been remedied and acknowledged via "Trip reset" /
"Autoreset".
The signal bit is updated continuously.
The signal bit is updated continuously.
The device receives control commands via the inputs.
The signal bit is updated continuously.
There is asymmetry. The signal bit is updated
continuously.
E24
The motor is switched off due to asymmetry.
The signal bit is deleted when the cause for the switch-
off has been remedied and acknowledged via "Trip
reset".
E7
Limit value exceeded.
The signal bit is updated continuously.
E8
Limit value undershot.
The signal bit is updated continuously.
E24
The signal bit is deleted when the cause for the switch-
off has been remedied and acknowledged via "Trip
reset".
E24
Switch-off, blocking current detected longer than
permissible blocking time. The signal bit is deleted when
the cause for the switch-off has been remedied and
acknowledged via "Trip reset".
Input stati:
"1" = active, HIGH level applied
"0" = inactive, LOW level applied
The signal bit is updated continuously.
There is a ground fault.
The signal bit is updated continuously.
E24
The motor is switched off due to a ground fault.
The signal bit is deleted when the cause for the switch-
off has been remedied and acknowledged via "Trip
reset".