Commissioning
5.2

Switching on for the First Time

5.2.1 Recommendation on Procedure for 3RW44 Commissioning

Suggested setting
Start
voltage %
Application
Conveyor belts
70
Powered roller
60
conveyors
Compressors
50
Small ventilators
30
Pumps
30
Hydraulic pumps
30
Stirrers
30
Centrifugal machines 30
Milling machines
30
Large fans
30
Mills
50
Crushers
50
Disk saws/ribbon
30
saws
5-4
Warning
Before switching the device on for the first time, verify that the main/control
side is wired properly. Make sure that the supply and control voltage comply
with the device-specific requirements (Chapter 10.3 "Technical Data").
Starting parameters
Starting mode: Voltage ramp and current limiting
(U+current limiting)
Starting
Current
time s
limit value
Deacti-
10
vated
Deacti-
10
vated
4 x I
10
4 x I
10
4 x I
10
4 x I
10
4 x I
30
4 x I
30
4 x I
30
4 x I
60
4 x I
60
4 x I
60
4 x I
60
Notice
This table provides example set values. They serve as reference for informational
purposes only and are non-binding. The set values depend on the particular application
and must be optimized during commissioning.
Breakaway pulse
Deactivated (0 ms) Torque control
Deactivated (0 ms) Torque control
Deactivated (0 ms) Coasting down
e
Deactivated (0 ms) Coasting down
e
Deactivated (0 ms) Pump stop
e
Deactivated (0 ms) Coasting down
e
Deactivated (0 ms) Coasting down
e
Deactivated (0 ms) Coasting down
e
Deactivated (0 ms) Coasting down
e
Deactivated (0 ms) Coasting down
e
80 % / 300 ms
e
80 % / 300 ms
e
Deactivated (0 ms) Coasting down
e
Stopping parameters
Stopping mode
Stopping
time s
10
10
X
X
10
X
X
X
X
X
Coasting down
X
Coasting down
X
X
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04
Parameter
Stopping
torque %
10
10
X
X
10
X
X
X
X
X
X
X
X